Which generator is right for me?
Published October 3, 2026.
Built by Jeremy Panasuk.
The right class is the one that clears your list. The path below starts at 2,000 W and only leaves that class when a published row forces it.
The list that is actually 2,000 W
- Running total = 192 + 700 = 892 W.
- Largest start is the furnace fan at 1,400 W, which is higher than the fridge's 1,200 W. Extra surge = 1,400 − 700 = 700 W.
- Peak = 892 + 700 = 1,592 W.
- 1,592 × 1.20 = 1,910 W, rounded up to the next 500 W = 2,000 W recommended.
Honda marks that furnace-fan row 240 V. A 120 V inverter can cover the fridge's 1,200 W start and still miss the fan, because the fan is not a 120 V load on Honda's chart. The fridge alone, without the fan, is the 1,500 W case on generator vs battery backup. Gasoline at 50% of this 2,000 W recommendation lasts 14.0 hours on a 4 gallon tank. Propane at 1.37 times the gasoline rate lasts 10.2 hours on the same 4 gallons. Those fuel lines are the home calculator, walked on how much propane a generator uses.
If you will not run the fan and the fridge's compressor start in the same moment, the load sequencer is the other tool. It uses the same highest-start extra as the home calculator, then stages rows into always, wait, and never-overlap. The 2,000 W figure above is the home calculator, with both rows on.
Branches that change the class
You are only keeping food cold and a few small 120 V loads. Stay with the fridge page and the camping list. A fan, a laptop, and a radio size to 1,000 W on best portable generator for camping. A battery with a published watt-hour rating, matched to the same 192 W fridge, is on best solar generator. That page is one sheet, not a test.
You want the furnace fan, and it is the 240 V row. The generator needs 240 V output. The watt recommendation is still 2,000 W until you add more rows. A transfer switch is required if those loads are on household circuits. Cord-versus-switch is on backup generator installation.
You want central air. Champion's 4-ton row, at the top of the band, plus the fridge, sizes to 10,000 W on 10 kW generator for a home. The peak is 8,192 W. Adding Honda's 4,500 W water heater moves that page to 15,500 W. Do not keep the 2,000 W answer once the condenser is on the list.
You are away when the power fails, and you want the set to start itself. That is a standby, not a bigger portable of the same 2,000 W. The watts still come first. One dryer-plus-4-ton-plus-fridge list sizes to 16,500 W and is compared with Generac's 20,000 W LP / 18,000 W natural-gas ratings on 20 kW home standby. Portable versus automatic, as an install choice, is on portable vs standby.
The tools are a saw and a washer, not a house. Honda's 10-inch table saw and 1 hp pressure washer size to 7,000 W on how to size an industrial generator. A building service is the point where that page tells you to stop and hire an engineer.
You are above 1,000 feet, or the set will sit near a property line. Derate is a separate step from the watt recommendation. The script's thresholds are on altitude derate. A published decibel rating and the distance formula are on noise at the lot line. Neither tool changes the 1,592 W peak. They change whether a nameplate that looked large enough still is, and whether the neighbor's lot line is the constraint.
A common mistake
Buying a 20 kW standby because a neighbor did, while the list in front of you is a fridge and a furnace fan. Those two rows are a 2,000 W recommendation. The 20 kW sheet is the right comparison only after the load list, the 240 V loads, and the wish for automatic start are actually on the table. The other mistake is dropping the furnace fan's 240 V mark and shopping a 120 V inverter whose watt rating happens to say 2,200.
Limits, and when to call a pro
Nameplates beat chart rows. If the fan motor is not the 1/3 hp row, do not keep 700 and 1,400. Re-enter the plate on the calculator. Connecting any of these sets to a panel takes a licensed electrician and a permit where local code requires one. Outdoors, at least 20 feet from the house, is still the portable rule on how to run a generator safely. An outage sequence for the first hours, food in a closed fridge, and what to do when utility power returns is on how to use a generator when the power goes out.
Compiled with AI assistance from the sources below. Spot an error? Email [email protected].
Sources
- Honda, What wattage generator do I need? — fridge and 1/3 hp furnace-fan rows
- GeneratorSizer calculator script —
sizeGenerator(), the 20% headroom and the 500 W round-up